Lamothe Approvals Inc.
formerly M.A. Lamothe & Associates Inc.

Worldwide Safety Approvals & Consulting Since 1979

Common Test Failures

Moe Lamothe, P.Eng, Lamothe Approvals Inc.

We often see the same failures and problems occurring in equipment we are testing. The following failures and some suggested solutions to these failures should be considered before you submit the equipment to us or any other testing agency.

Dielectric Strength

The purpose of the dielectric strength test  (also known as electric strength test or hi-pot test) is to verify adequate creepage and clearance distances so that at some point in the future, the product will not become a safety hazard due to a breakdown from primary to ground or secondary.

In theory, all of the necessary distances can be verified by inspection but due to the large numbers of areas to be investigated this is not always practical and a visual inspection does not always find production problems. Some of the older standards only specify a dielectric strength test with no investigation of creepage or clearance.

It is essential that you verify the dielectric strength of your product prior to submitting it for testing. The applicable standard will give you the appropriate values to use. Common values are 1,500Vac (or 2121Vdc) primary to ground and 3,000Vac (or 4242Vdc) primary to secondary, but these will vary depending on the safety standard used.

Transformer Overload

The secondary windings of mains transformers are short-circuited and subjected to any overloads that may arise from any fault condition. Windings are tested in turn, one at a time, to simulate short circuits or overloads. All other windings are loaded or not loaded, whichever load condition is the least favourable. Short-circuits or loads are applied on the load side of any current-limiting impedance or over-current protective device which is connected directly to the winding.

For the short circuit test, any input fuse or protector is left in-place and in most cases the protector opens. We have seen cases where with a short on the output of the transformer, the input did not draw enough current to open the fuse - it makes us wonder what the designer thought he was protecting!

For the overload test, the secondary of the transformer is loaded so that the primary draws 135% (based on North American characterized protector) or 150% (based on IEC characterized protector) of the input protector (fuse or circuit breaker). The protector is removed for this test.

This test frequently results in a failure, usually because the transformer flames. An opened primary winding is acceptable as long as the allowable temperature of the transformer winding during the fault are not exceeded before opening. With multiple winding transformers it is usually necessary to include a thermal protector in the primary winding or a fuse in each secondary winding.

AVOID EMBARRASSMENT - RUN THESE SIMPLE TESTS BEFORE YOU SUBMIT YOUR PRODUCT FOR SAFETY TESTING!  

Moe Lamothe is the president of Lamothe Approvals Inc. (Georgetown, ON, Canada). He can be reached at info@lamotheapprovals.com.

More Articles

COPYRIGHT NOTICE

The copyright for all of the text, tables and illustrations remains with Lamothe Approvals Inc. Permission is granted to print or reproduce this document provided that it properly attributed to Lamothe Approvals Inc.

Prepared May 2003